Detail
Summary
AG1800 is designed to generate multiple diameters aerosol for testing HEPA filtration system by combination with TDA-2I photometer, with safest oil insurance supply system and heat interchange function. AG 1800 is ideal for certifying or testing HEPA filters or installations with air flows from 1,500 to 65,000 cfm. It requires an inert gas source and AC220v±10%50HZ power source.
Specification
Application
leakage detecting for clean-room, laminar flow bench, biosafety cabinet, glove box, HEPA vacuum cleaner, HVAC system, ULPA/HEPA filters, negative filtration device, operation room, nuclear filtration system, collective protection filters, etc.
AG1800 is designed to generate multiple diameters aerosol for testing HEPA filtration system by combination with TDA-2I photometer, with safest oil insurance supply system and heat interchange function. AG 1800 is ideal for certifying or testing HEPA filters or installations with air flows from 1,500 to 65,000 cfm. It requires an inert gas source and AC220v±10%50HZ power source.
Specification
Air flow range | 1,500-65,000cfm(42-1,839.5m3/min) |
Aerosol concentration | 10ug/L: 65,000cfm(1,839.5m3/min) |
100ug/L: 6,500cfm(183.95 m3/min) | |
Aerosol type | PAO, DOP, Polydispensed |
Generator type | vapor condensation |
Compressed air(inert) | Nitrogen, Argon, Carbon Dioxide or Helium (50psi)) |
Power source | AC220v±10%50HZ |
Overall dim.(mm) | 280×390×300 |
Weight (kg) | 14 |
Application